DC voltage drop calculator
Result
Enter the supply voltage, current and cable details to see the result.
Working
V_drop = I × R, where R = r × 2 × L × k
- r is the resistance of one conductor per metre. It comes from the cable size (BS EN 60228, plain copper, at 20 °C).
- L is the length of the run. The current goes out and back, so the sum uses twice this.
- k is 1 for a cable at 20 °C. For a hot cable at 70 °C it is 1.20, taking 0.4% more resistance for each degree.
- I is the load current in amps.
For a fire alarm sounder circuit or a door lock, use the sounder circuit calculator or the lock cable calculator. They ask for the minimum voltage the equipment needs and say whether the circuit passes.
For guidance only. Always check against the current edition of the standard and the manufacturer's data.