Calculator · BS EN 60228 cable data
DC voltage drop calculator
Quick answer
Voltage drop is the current times the resistance of the cable there and back (its resistance per metre times twice the run length). Take it from the supply voltage to get the voltage left at the load, and check that against the device's minimum working voltage.
Enter the supply voltage, the current the load draws, the cable size and the length of the run. You get the voltage lost in the cable, the voltage left at the load, and the longest run for a drop you choose. It shows every step. It uses the maximum resistance for copper cable, so check the answer against the equipment's data sheet.
Result
Enter the supply voltage, current and cable details to see the result.
Working
V_drop = I × R, where R = r × 2 × L × k
- r is the resistance of one conductor per metre. It comes from the cable size (BS EN 60228, plain copper, at 20 °C).
- L is the length of the run. The current goes out and back, so the sum uses twice this.
- k is 1 for a cable at 20 °C. For a hot cable at 70 °C it is 1.20, taking 0.4% more resistance for each degree.
- I is the load current in amps.
For a fire alarm sounder circuit or a door lock, use the sounder circuit calculator or the lock cable calculator. They ask for the minimum voltage the equipment needs and say whether the circuit passes.
For guidance only. Always check against the current edition of the standard and the manufacturer's data.