Emergency lighting · BS 5266-1
Emergency lighting test frequencies explained: monthly, annual and five-yearly
Quick answer
Emergency lighting gets a function test every month (every luminaire switches to emergency mode), a full-duration test every year (each stays lit for its rated time, usually 3 hours, on battery), and a light level check at least every five years. BS 5266-1:2025 is the code of practice; the testing follows BS EN 50172:2024.
The tests and how often
BS 5266-1:2025 (October 2025) replaced the 2016 edition and sets the overall code of practice. The testing itself follows BS EN 50172:2024. Maintenance comes down to two recurring tests, a light check every few years, and a look at whether the installation still matches the building:
| Test | What it proves | How often |
|---|---|---|
| Function test | Every luminaire switches to emergency mode when the supply is interrupted | Monthly |
| Full-duration test | Every luminaire stays lit for its rated duration (usually 3 hours) on battery alone | Annually |
| Light level check | The light on escape routes and in open areas still meets the minimum levels | At least every five years |
The monthly test is short: long enough to see each fitting light up, not long enough to drain the battery. The annual test runs for the full rated duration and is the one that reveals a tired battery.
The emergency lighting test due calculator works out when the next monthly and annual tests are due from the last ones done, and the test schedule and duration helper lays out a whole year of dates and tells you whether the annual test is 1 hour or 3. Record them in the free emergency lighting test log.
The monthly function test
Interrupt the normal supply to the emergency luminaires (usually with a test key switch), confirm every fitting and exit sign lights up, restore the supply, and confirm the charging indicators come back on. Check every exit sign is readable, and that nothing is damaged, missing or blocked. Any fitting that fails to light is recorded and fixed.
This is normally done by the responsible person on site and logged in the site's emergency lighting log book. It does not need an engineer, but it does need doing: a year of missing monthly entries is a common audit finding. Make sure the person doing it knows how, and that it goes in the log book every time.
The annual full-duration test
Once a year a competent person runs each luminaire on battery for its full rated duration and checks every fitting is still lit at the end. The rated duration is:
- 1 hour where everyone leaves straight away and the building is not used again until the batteries have recharged;
- 3 hours where people cannot all leave at once (anywhere people sleep, for example) or the building is used again before the batteries are back to full.
If in doubt, it is 3 hours. Fittings that go dark early have batteries that no longer hold their rated capacity: they need new batteries or replacing, and the failures go in the log book with what was done.
Timing the test: because the batteries need time to recharge afterwards (up to 24 hours), do the annual test when the building can manage with reduced emergency cover for the recharge period. That usually means outside occupied hours, or testing alternate fittings, or in stages across a building with more than one circuit.
For self-contained luminaires the result is per fitting. For central battery systems the duration test is on the central unit, with the individual fittings checked for light, and the battery readings recorded.
Every five years: measure the light again
This is the one people miss. BS 5266-1:2025 asks for the system's light levels to be verified at commissioning and again at intervals of no more than five years, and BS EN 50172:2024 (clause 7.4.5) sets the measurement every five years. Fittings age, rooms get repartitioned and racking goes up in front of fittings, so a system that met the levels when it went in may not now.
Take readings along the escape routes and in open areas, and compare them with the minimums in how much light emergency lighting needs. The emergency lighting lux checker does the comparison, and the exit sign viewing distance calculator checks the signs can be read from the far end of the route.
Central battery systems: the readings
Where a site has a central battery unit rather than self-contained fittings, the annual visit should record float voltage, on-load voltage, charger output and the load current, and assess whether the battery capacity still meets the design duration. As with fire alarm standby batteries, the assessment is a calculation from the readings. Writing the numbers down without doing the sum leaves the certificate unable to say whether the system is compliant.
Does the installation still match the building?
Emergency lighting is designed around escape routes, open areas and high-risk task areas. Buildings change: a new partition wall, a re-hung door or a rearranged warehouse can leave part of an escape route unlit. The annual visit should include a walk of the escape routes against the current layout, and the certificate should say whether coverage is still adequate. The five-yearly light measurements then show whether the levels still hold.
Automatic test systems
Self-test fittings and addressable systems do the monthly and annual tests on a schedule and log the results. They do not remove the need for someone to look at the results, deal with failures and keep the record, and they do not do the five-yearly light measurements for you.
What changed in the 2025 edition
- Local area lighting and standby lighting are now in scope. Local area lighting is for finishing a dangerous task safely, or staying put where people do not need to leave at once; standby lighting keeps normal work going in a mains failure.
- Photometric verification (the five-yearly measurements above) is asked for.
- Words: "deviation" is now "variation", "refuges" are "temporary waiting spaces" and "open area lighting" is "emergency local area lighting".
- Handover: the commissioning inspection and test results (to BS EN 50172:2024) go in the handover documents, with any variations clearly identified.
- Adaptive escape lighting is recognised.
What the record has to show
- The site and system, and whether it is self-contained or central battery
- The date, the type of test (function, full-duration or light measurement), and who carried it out
- A luminaire-by-luminaire result for the annual test, including the duration achieved
- Central battery readings and the resulting capacity assessment, where applicable
- Every defect, with a severity and recommended action, and what was done about it
- Any alterations to the system
- An overall verdict and the next test due date
A paper log book, a printout from an automatic test system or a digital log are all recognised. If you need a paper one, the emergency lighting log book is free to print.
Kerova's emergency lighting certificate holds the luminaire register, the duration results and the central battery readings, computes the verdict, and reminds the client before the next annual test is due.
This guide is general information for UK fire & security companies, not legal or engineering advice. Always work to the current edition of the relevant standard and your own competent-person judgement.
Doing it on site?Doing the emergency lighting certificate? Do it on your phone with Kerova's emergency lighting certificate software, part of its fire and security software. The register, readings and result are built into the certificate itself.
Start free trialRelated
- Emergency lighting test schedule and duration helper
- Emergency lighting test due date calculator
- Emergency lighting monthly and annual test log (free PDF)
- Emergency lighting log book to print
- Emergency lighting lux checker
- Exit sign viewing distance calculator
- How much light does emergency lighting need?
- Emergency lighting certificates in Kerova
- Fire alarm servicing intervals
- What makes a certificate compliant?
- Fire risk assessment software for assessors (coming to Kerova)
- Building compliance software: everything Kerova does