Fire alarm · BS 5839-1
What goes on a BS 5839-1 service certificate
Quick answer
After each inspection and servicing visit the engineer leaves a certificate. BS 5839-1 gives a model but doesn't insist on its layout: what matters is a record someone else can pick up months later and see what was looked at, what was tested, what was wrong and what was left for the site to sort out. It covers the service, not whether the whole system meets the standard.
The short version
After each inspection and servicing visit to a fire alarm, the engineer leaves a certificate. BS 5839-1 gives a model, but doesn't insist on its layout. What it does need is a record that someone else can pick up months later and see exactly what was looked at, what was tested, what was wrong, and what was left for the site to sort out.
The certificate covers the service. It isn't a statement that the whole system meets the standard: that's for the design and commissioning paperwork (see which certificate each job needs).
What goes on it
| Part | What to record |
|---|---|
| The premises | Site name and address, and the responsible person. |
| The system | Category (L1 to L5, M, P1, P2), panel make and model, number of zones, and whether it signals to an alarm receiving centre. |
| The visit | Date, the engineer and their company, and the certification body if the company has one. |
| What was tested | Which zones and devices were tested this visit, with the results. Over 12 months, every device should be covered, so "a sample" isn't enough: say which. |
| Call points, sounders and interfaces | Manual call points, sounders and beacons, and anything the system controls: door holders, shutdowns, the signal to the alarm receiving centre. |
| Standby power | Battery readings and the capacity worked out from them, the battery's age, and whether it's still big enough. |
| The log book | That it was read, and the false alarms, faults and disablements since the last visit. |
| False alarms | How many in the last 12 months against the number of detectors, and whether that calls for a closer look. |
| Variations | Any agreed variations from the standard, carried over so they aren't lost. |
| Defects | Each one on its own line, how serious it is, and what's recommended. Not a line of free text at the bottom. |
| How it was left | Whether the system is back to normal, and anything still disabled. |
| Signatures and next visit | The engineer's signature, the responsible person's, and when the next service is due. |
The weekly test and day-to-day events go in the site's log book, not on the certificate. The free fire alarm weekly test and event logbook has room for both.
The battery sum, not just the readings
The most common gap on paper certificates is a page of battery voltages with no sum done. Writing down the readings doesn't say whether the battery can carry the system through a power cut: the required capacity has to be worked out from the standby and alarm currents and the times, and compared with what's fitted. The fire alarm battery calculator shows the method and the working. The 2025 edition also recommends marking each battery with the date it was fitted (see what's changed in 2025).
Where service certificates usually go wrong
- "All devices tested" with no list, on a system that's clearly been sampled.
- Battery readings with no capacity worked out, or a five-year-old battery passed without comment.
- No mention of false alarms, when the log book shows several.
- Defects in a notes box, with no severity and no recommendation, so nobody acts on them.
- Disablements left in place and not written down.
- No next service date, and no signature from the site.
Most of these come from filling the certificate in afterwards from memory. Filling it in on site, as you go, fixes nearly all of them. The service visit checklist puts the checks in the order you'd do them.
How Kerova's service certificate does it
In Kerova the engineer fills the certificate in on their phone during the visit, starting from last visit's zones and panel details. Each zone and device gets a result, the battery capacity is worked out from the readings, fails become defects with a severity, and the overall result is worked out from what was tested. The client signs on screen, the certificate is locked once signed, and anyone can check it's genuine with the QR code on it. It works with no signal and sends when you're back in range.
Common questions
Do I have to use the certificate layout in the standard?
No. BS 5839-1 gives model certificates, but your own layout is fine as long as it records the same things. What matters is that someone reading it later can see what was tested, what was found and who signed it.
Who signs the service certificate?
The competent person who did, or is responsible for, the servicing. The responsible person on site should sign or acknowledge it too, especially where defects are left for them to deal with.
How often is one issued?
After every inspection and servicing visit, so usually every six months. Every device should have been tested at least once over any 12 months, and the certificates together should show that.
Does a service certificate say the system complies with BS 5839-1?
No. It says the system was inspected and serviced, and records what was found. Whether the design meets the standard is a separate question, for the design certificate or a full inspection.
This guide is general information for UK fire & security companies, not legal or engineering advice. Always work to the current edition of the relevant standard and your own competent-person judgement.
Doing it on site?Doing the fire alarm certificate? Do it on your phone with Kerova's fire alarm certificate software, part of its fire and security software. The register, readings and result are built into the certificate itself.
Start free trialRelated
- Fire alarm weekly test and event logbook (free PDF)