Calculator · Fire extinguishers · BS 5306-3

Fire extinguisher service due date calculator

Choose the kind of service and the type of extinguisher, then enter the date of the last one. You get the date the next is due. A basic service is yearly. An extended service is every five years, and a CO2 extinguisher is overhauled every ten years.

Your figures

The last service of the kind chosen above.

Result

Choose the date of the last service to see the result.

Working

next due = last service + 1 year (basic) · + 5 years (extended) · + 10 years (CO2 overhaul)

  • Basic service: once a year, by a competent person.
  • Extended service: every 5 years for water, foam, wet chemical and powder extinguishers.
  • CO2 overhaul: every 10 years, with a hydraulic pressure test.
  • Between services, the Responsible Person checks each extinguisher by eye every month.

Source: BS 5306-3:2017, as set out by the FIA and BSI. Some sealed powder extinguishers have a different extended service interval. Check the maker's instructions.

Servicing follows the maker's instructions as well as BS 5306-3. Keep the service record with the extinguisher.

For guidance only. Always check against the current edition of the standard and the manufacturer's data.