Calculator · Emergency lighting · BS 5266-1

Emergency lighting test due date calculator

Choose the test and enter the date it was last done. You get the date the next one is due. Emergency lighting has a monthly function test, an annual full-duration test and a five-yearly photometric check.

Your figures

Result

Choose the date of the last test to see the result.

Working

next test = last test + 1 month · + 12 months · + 5 years

  • Monthly: a short function test of every luminaire and exit sign.
  • Annual: a full-duration test, where the luminaires run on battery for their rated duration.
  • Every five years: a photometric check, measuring the light levels again.
  • Rated duration: 1 hour where the building is emptied at once and not used again until the batteries have recharged. 3 hours where people cannot leave at once, or where the building is used again before the batteries recharge.

Source: BS 5266-1:2025 (photometric checks at intervals not exceeding five years, as quoted by NICEIC) and BS EN 50172:2024 clause 7.4.5, as set out by NICEIC and emergency lighting makers. The 1 hour and 3 hour rule is from industry guides, and no clause number was found.

Record every test in the log book. To check a reading, use the lux checker.

For guidance only. Always check against the current edition of the standard and the manufacturer's data.

Built by the engineer behind Kerova, certificate software for fire and security firms.