Fire alarm · BS 5839-1

How many smoke detectors does a room need?

How far a detector reaches, how far apart they go, how close to a wall, and how to count the detectors a room needs, with a worked example.

How far does a detector reach?

Every point in a protected area should be within 7.5 m (measured across the floor) of a smoke or CO detector, or within 5.3 m of a heat detector. Laid out on a square grid, that means about 10.6 m between smoke detectors and about 7.5 m between heat detectors. These figures are the same in BS 5839-1:2025 as in the 2017 edition.

The 10.6 m comes from the 7.5 m reach: a detector covers a square whose corners are 7.5 m away, so each side is 7.5 × √2, about 10.6 m.

Counting the detectors for a room

For an empty rectangular room with a flat ceiling, divide each side by the 10.6 m grid and round up:

  1. Detectors along the length = length ÷ 10.6, rounded up
  2. Detectors across the width = width ÷ 10.6, rounded up
  3. Multiply the two numbers together

Example: a room 24 m long and 12 m wide. Along the length, 24 ÷ 10.6 rounds up to 3. Across the width, 12 ÷ 10.6 rounds up to 2. That is 3 × 2 = 6 smoke detectors, each covering a box of about 8 m by 6 m.

The free detector spacing calculator does this and draws the layout. Treat the answer as a planning count, not a design. Real rooms have walls, beams, doors and furniture that change where detectors can go.

How close to a wall?

A detector should not be within 500 mm of a wall, or of anything that counts as a wall, such as a deep beam or a partition that stops short of the ceiling.

An obstruction counts as a wall if the gap above it is under 300 mm and its depth is more than 10% of the ceiling height. Keep detectors at least twice the depth away from an isolated obstruction up to 250 mm deep.

Narrow corridors

In a corridor under 2 m wide the coverage areas do not need to overlap, so smoke detectors can be about 15 m apart and heat detectors about 10.6 m. A corridor wider than 2 m is treated as a room, and the grid above applies.

Ceiling height limits

DetectorNormal limitOver up to 10% of the area
Point smoke or CO10.5 m12.5 m
Heat, class A19 m10.5 m
Heat, other classes7.5 m10.5 m

A multi-sensor that works on heat and smoke only takes the heat limit.

What changed in 2025

  • Category L2 now includes rooms where people sleep. The standard now recommends smoke, multi-sensor or CO detectors there, and heat detectors only if a fire risk assessment justifies them. It is not retrospective.
  • Stairway lobbies now need automatic detection.
  • A firmware update to the control panel counts as a modification and needs a certificate.

Common questions

How many smoke detectors do I need in a room?

For an empty flat-ceilinged room, divide each side by about 10.6 m and round up, then multiply. A 24 m by 12 m room needs 3 × 2 = 6. A design has to allow for walls, beams and other obstructions.

How far apart should smoke detectors be?

About 10.6 m on a square grid, because no point should be more than 7.5 m from a detector. In a corridor under 2 m wide they can be about 15 m apart.

How close to a wall can a smoke detector be?

Not within 500 mm of a wall, or of anything treated as a wall, such as a deep beam or a partition that stops short of the ceiling.

What is the highest ceiling a smoke detector can be fitted under?

10.5 m, or 12.5 m over up to 10% of the area, for point smoke and CO detectors.

This guide is general information for UK fire & security companies, not legal or engineering advice. Always work to the current edition of the relevant standard and your own competent-person judgement.