How emergency lighting is designed, installed, tested and recorded: what light levels are needed on escape routes and in open areas, how long the lights must last on battery, and how often the system is tested.
The rules for the lights that come on when the power fails: how bright they must be, how long they must last, and how often they are tested.
BS 5266-1:2025, BS EN 1838:2024. BS 5266-1:2025 (October 2025) replaced the 2016 edition. BS EN 1838:2024 replaced the 2013 edition. Testing follows BS EN 50172.
Confirmed two or more sources agree, or a source quotes the standard. Check one source, or a detail that could not be confirmed. Check it against the standard.
At least 1 lux across the whole width of the route, less a border: 0.5 m each side for routes over 2 m wide, and a quarter of the width each side for routes up to 2 m wide. This is the 2024 edition, which lights the whole width. The 2013 edition measured the centre line.
At least 1 lux on the floor across the route, leaving out a margin at each edge. Older guides say the centre line only. That changed in 2024.
The 2024 edition lights the whole width of the route, less a border. The 2013 edition measured the centre line only.
At least 0.5 lux across the space, leaving out a 0.5 m border. The 2024 edition also asks for the shortest obvious route through the area to be lit as an escape route.
Enough light to find the way out of a large open space: at least 0.5 lux, and the shortest route to the exit lit like an escape route.
The brightest reading divided by the dimmest along an escape route should not be more than 40 to 1. This is confirmed for the 2013 edition and was not found quoted for 2024.
The light should not be patchy. The brightest spot should be no more than 40 times the dimmest.
Confirmed for the 2013 edition only. Check the 2024 wording.
1 hour where the premises are emptied at once and not used again until the batteries have recharged. 3 hours where people cannot leave at once, such as sleeping accommodation, or where the building is used again before the batteries recharge.
One hour if everyone leaves straight away and nobody goes back in until the batteries are charged. Three hours if people sleep there or cannot leave quickly.
The rated duration is 1 hour or 3 hours, depending on how the building is used.
Yes. BS 5266-1:2025 asks for the photometric performance to be verified at commissioning and at intervals not exceeding five years, and BS EN 50172:2024 (clause 7.4.5) says illuminance measurements are made once every five years.
Every five years, measure the light again to show the system still does its job.
Local area lighting and standby lighting are in scope, photometric verification is asked for, 'deviation' became 'variation', commissioning results must be in the handover documents, and borrowed light is excluded. Adaptive escape lighting is now recognised.
The new edition adds local area and standby lighting, asks for light measurements every five years, says 'variation' instead of 'deviation', and wants the test results handed over.
A completion certificate (made up of design, installation and verification declarations), a small installations certificate for up to 25 self-contained luminaires, a periodic inspection and testing certificate, and a certificate for verifying an existing installation.
There is a certificate for finishing a new system, a shorter one for small systems, one for each inspection and test, and one for checking an existing system.
New in the 2025 scope. Local area lighting lets people safely finish vital tasks or stay where they are when they do not need to leave at once. Standby lighting lets normal activity carry on when the mains fails.
Local area lighting is for finishing a dangerous job safely or staying put. Standby lighting lets you carry on working as normal.
Guidance from the 2016 edition and EN 1838:2013 lists exits and outside final exits, stairs (so each step is lit), changes of direction or level and corridor intersections, first aid points, fire equipment and call points, alarm panels, disabled toilets and toilets over 8 m², generator, switch and control rooms, escalators and covered car-park routes. Lifts are included only when they are in the evacuation plan.
Light exits, stairs, corners, changes of level, first aid, fire equipment and call points, alarm panels, big and disabled toilets, plant rooms, escalators and covered car-park routes.
Emergency lighting goes at exits and outside final exits, on stairs, at changes of direction and level, at first aid points, fire equipment and call points, and in larger toilets and generator, switch and control rooms.
The list is from the 2016 edition and EN 1838:2013. Check the 2025 wording.
A maintained luminaire works all the time. A non-maintained luminaire works only when the mains fails. A combined (sustained) luminaire has one lamp kept for emergency use. Maintained signs are favoured in licensed, entertainment and sleeping premises.
Maintained lights are always on. Non-maintained lights come on only in a power cut. Combined ones have a spare lamp for emergencies.
Maintained lights are always on. Non-maintained lights come on only in a power cut. Combined ones keep one lamp lit.
'Deviation' is now 'variation'. 'Refuges' are now 'temporary waiting spaces'. Handover must include commissioning results, variations and plans showing signs.
The words changed: deviation became variation and refuge became temporary waiting space. Hand over the test results and sign plans.