Quick reference · Emergency lighting

BS 5266-1 and BS EN 1838: quick reference

How emergency lighting is designed, installed, tested and recorded: what light levels are needed on escape routes and in open areas, how long the lights must last on battery, and how often the system is tested.

The rules for the lights that come on when the power fails: how bright they must be, how long they must last, and how often they are tested.

BS 5266-1:2025, BS EN 1838:2024. BS 5266-1:2025 (October 2025) replaced the 2016 edition. BS EN 1838:2024 replaced the 2013 edition. Testing follows BS EN 50172.

Confirmed two or more sources agree, or a source quotes the standard. Check one source, or a detail that could not be confirmed. Check it against the standard.

How much light does an escape route need?

At least 1 lux across the whole width of the route, less a border: 0.5 m each side for routes over 2 m wide, and a quarter of the width each side for routes up to 2 m wide. This is the 2024 edition, which lights the whole width. The 2013 edition measured the centre line.

At least 1 lux on the floor across the route, leaving out a margin at each edge. Older guides say the centre line only. That changed in 2024.

The 2024 edition lights the whole width of the route, less a border. The 2013 edition measured the centre line only.

ConfirmedEmergency lighting lux checker →

How much light does an open area need?

At least 0.5 lux across the space, leaving out a 0.5 m border. The 2024 edition also asks for the shortest obvious route through the area to be lit as an escape route. BS 5266-1:2025 brings open areas under 60 m² into scope too, where a fire risk assessment says emergency lighting is needed there.

Enough light to find the way out of a large open space: at least 0.5 lux, and the shortest route to the exit lit like an escape route. Since 2025, even a small open area under 60 m² can need it, if the fire risk assessment says so.

ConfirmedEmergency lighting lux checker →

What about fire equipment and call points?

At least 5 lux, measured vertically, near fire-fighting equipment, call points, door releases, rescue plans, first aid boxes and safety equipment for disabled people. BS 5266-1:2025 adds its own explicit figure for public swimming pools: 5 lux at the water surface and along the pool's circulation routes.

Places where someone needs to see and use something need at least 5 lux, measured on the upright surface — including first aid boxes. Public swimming pools now have their own explicit figure too: 5 lux at the water surface and around the pool.

ConfirmedEmergency lighting lux checker →

What about high-risk task areas?

The higher of 15 lux and 10% of the task's normal lighting level, measured on the working plane. For example, a task normally lit to 500 lux needs at least 50 lux of emergency lighting. This carries over unchanged into BS EN 1838:2024.

Where a dangerous job is done, keep at least 15 lux or a tenth of the normal light, whichever is more. A desk normally lit to 500 lux needs at least 50 lux in an emergency.

ConfirmedEmergency lighting lux checker →

How long must emergency lighting last?

1 hour where the premises are emptied at once and not used again until the batteries have recharged. 3 hours where people cannot leave at once, such as sleeping accommodation, or where the building is used again before the batteries recharge.

One hour if everyone leaves straight away and nobody goes back in until the batteries are charged. Three hours if people sleep there or cannot leave quickly.

The rated duration is 1 hour or 3 hours, depending on how the building is used.

No clause number was found for this rule.

ConfirmedEmergency lighting test due date calculator →

How often is emergency lighting tested?

A functional test every month, and a full-duration test every year by a competent person. Results go in the log book.

Check every light works each month, and once a year run them on battery for their full time.

Test every month, run the full duration once a year, and measure the light again every five years.

ConfirmedEmergency lighting test due date calculator →

What changed in BS 5266-1:2025?

Local area lighting and standby lighting are in scope, photometric verification is asked for, 'deviation' became 'variation', commissioning results must be in the handover documents, and borrowed light is excluded. Adaptive escape lighting is now recognised.

The new edition adds local area and standby lighting, asks for light measurements every five years, says 'variation' instead of 'deviation', and wants the test results handed over.

Confirmed

How far away can an exit sign be read?

200 times the height of the pictogram for an internally illuminated sign, and 100 times the height for an externally illuminated sign. A sign with a 175 mm pictogram, for example, reads from about 35 m internally lit or 17.5 m externally lit.

A 15 cm running man on a lit sign can be seen from about 30 m. On a sign lit from outside, about 15 m.

The distance is set by the height of the running man, not the whole sign. Example: a 150 mm figure.

ConfirmedExit sign viewing distance calculator →

Which certificates are there?

A completion certificate (made up of design, installation and verification declarations), a small installations certificate for up to 25 self-contained luminaires, a periodic inspection and testing certificate, and a certificate for verifying an existing installation.

There is a certificate for finishing a new system, a shorter one for small systems, one for each inspection and test, and one for checking an existing system.

ConfirmedWhich certificate do I need? →

What are local area lighting and standby lighting?

New in the 2025 scope. Local area lighting lets people safely finish vital tasks or stay where they are when they do not need to leave at once. Standby lighting lets normal activity carry on when the mains fails.

Local area lighting is for finishing a dangerous job safely or staying put. Standby lighting lets you carry on working as normal.

Confirmed

What is different for central battery systems?

They must keep working through a circuit fault, and the source rating is given in watts and VA, allowing for power factor and inrush. BS 5266-1:2025 asks for that power supply calculation to account specifically for LED power factor, and for cable protected against mechanical damage to have a minimum impact rating of 5 joules.

A central battery system must keep going even if one circuit fails, and its rating must allow for start-up surges — now specifically accounting for how LEDs behave. The 2025 edition also sets a minimum toughness (5 joules of impact resistance) for cable protection against physical damage.

The LED power factor and 5 joule cable figures come from a single trade summary of the 2025 edition.

Check

Where is emergency lighting needed?

Guidance from the 2016 edition and EN 1838:2013 lists exits and outside final exits, stairs (so each step is lit), changes of direction or level and corridor intersections, first aid points, fire equipment and call points, alarm panels, disabled toilets and toilets over 8 m², generator, switch and control rooms, escalators and covered car-park routes. Lifts are included only when they are in the evacuation plan.

Light exits, stairs, corners, changes of level, first aid, fire equipment and call points, alarm panels, big and disabled toilets, plant rooms, escalators and covered car-park routes.

Emergency lighting goes at exits and outside final exits, on stairs, at changes of direction and level, at first aid points, fire equipment and call points, and in larger toilets and generator, switch and control rooms.

The list is from the 2016 edition and EN 1838:2013. Check the 2025 wording.

Confirmed

How many luminaires does an escape route need?

Each section of an escape route needs at least two light sources, so one failure does not leave it dark.

Every stretch of an escape route needs at least two lights, so one failing does not leave it in the dark.

Confirmed

What is the difference between maintained and non-maintained?

A maintained luminaire works all the time. A non-maintained luminaire works only when the mains fails. A combined (sustained) luminaire has one lamp kept for emergency use. Maintained signs are favoured in licensed, entertainment and sleeping premises.

Maintained lights are always on. Non-maintained lights come on only in a power cut. Combined ones have a spare lamp for emergencies.

Maintained lights are always on. Non-maintained lights come on only in a power cut. Combined ones keep one lamp lit.

Confirmed

Self-contained or central battery?

A self-contained luminaire's battery-to-lamp wiring is internal (or within 1 m, treated as internal), so it just needs to meet the general requirements of BS 7671 — no fire-resistant cable is called for. A central battery system is different: the cable carrying power out to every luminaire has to stay alive through a fire, so it is wired in fire-resistant cable, with two performance levels depending on the building.

Self-contained lights have their own battery built in, so the wiring to the lamp is treated as internal and uses ordinary cable. A central battery system feeds many lights from one big battery over a distance, so that cable has to be fire-resistant, or the whole system could go dark in a fire.

Self-contained lights carry their own battery. A central system feeds many lights from one battery and needs fire-resistant cable.

Confirmed

Which exit signs can be used?

The ISO 7010 green running man with an arrow, which BS 5266-1 adopted in its 2011 edition. Mixing this with the older BS 5499 style is only a recommendation against, not a legal requirement, but all the signs in one building should be a consistent style, size and format to avoid confusing people escaping. A sign with text only does not comply with the Health and Safety (Safety Signs and Signals) Regulations 1996, and needs replacing or pairing with a pictogram.

Use the green running man sign with an arrow, and keep the same style throughout a building — mixing the old and new sign styles is not illegal, but it is bad practice. Words-only signs do not comply with the safety signs regulations.

ConfirmedExit sign viewing distance calculator →

What wording changed in 2025?

'Deviation' is now 'variation'. 'Refuges' are now 'temporary waiting spaces'. 'Open area lighting' is now 'emergency local area lighting'. Handover must include the commissioning inspection and test results from BS EN 50172:2024, plus any variations, clearly identified.

The words changed: deviation became variation, refuge became temporary waiting space, and open area lighting became emergency local area lighting. Hand over the test results and a clear note of any variations.

Confirmed

Other guides: BS 5839-1, BS 5839-6, BS 5306 (extinguishers), BS EN 50131-1 and PD 6662, BS 8418, BS EN 62676-4, BS EN 60839-11-1, BS 7273-4, BS 7671 (for alarm and CCTV work). Not sure what a word means? Explain this text or see the glossary.

For guidance only. Always check against the current edition of the standard and the manufacturer's data.