Calculator · BS 5839-1:2025

Fire alarm battery calculator

Enter the standby and alarm current from the panel's data and choose the standby period. You get the minimum battery capacity by the BS 5839-1:2025 method, with every step shown. It doesn't know your panel, so check the answer against the manufacturer's data.

Your figures

Enter currents in
mA
mA
min

Default 30 minutes (0.5 h).

Advanced
D

Result

Enter the standby and alarm currents to see the result.

Working

Cmin = 1.25 × (T1 × I1 + D × I2 × T2)

  • Cmin is the minimum capacity when new, in Ah (20-hour rate, 20 °C).
  • 1.25 is the ageing factor: 5% a year over 4 years.
  • D is the de-rating factor. The default is 1.75, and you can change it under Advanced.
  • T1 is the standby period and T2 the alarm period, both in hours. I1 is the standby current and I2 the alarm current, both in amps.

Source: BS 5839-1:2025, clause 24 and Annex E.

For an intruder alarm panel, use the intruder alarm battery calculator. It uses the same method, with the intruder alarm standby hours.

BS 5839-1:2025 (clause 24.3.3) recommends marking batteries with their installation date. Writing it on the casing in permanent marker is acceptable.

For guidance only. Always check against the current edition of the standard and the manufacturer's data.