BS 5839-1:2025
BS 5839-1:2025: what's changed for installers
Quick answer
BS 5839-1:2025 replaced the 2017 edition in April 2025. Most of it reads the same, but a handful of changes alter what you fit, sign and record, such as sleeping rooms now coming into Category L2. None of it is retrospective: a system that met the 2017 edition doesn't have to be upgraded, though new work, extensions and modifications follow the new edition.
Overview
BS 5839-1:2025 replaced the 2017 edition in April 2025. Most of it reads the same, but a handful of changes alter what you fit, what you sign and what you write down. These are the ones that matter on site. None of them are retrospective: a system that met the 2017 edition when it went in doesn't have to be upgraded just because the standard changed. New work, extensions and modifications are another matter (see below).
Not sure which edition a document you've been handed refers to? The standards editions list has the current one for each.
Sleeping rooms are in L2 now
Category L2 now includes rooms where people sleep, and so do the sleeping rooms covered in an L3 design. In those rooms the standard now recommends smoke, multi-sensor or CO-fire detectors; a heat detector is only appropriate if the fire risk assessment justifies it.
In practice: on any new L2 or L3 job with bedrooms, hotel rooms or care rooms, don't default to heat detectors in the bedrooms. If the specification shows heat, ask for the risk assessment that backs it up, and record it.
The system categories reference has the 2025 note against each category.
Detection in stairway lobbies
The 2025 edition adds automatic detection in stairway lobbies. Check this on new designs and on extensions that take in a stair core.
A firmware update is a modification
Updating the control panel's firmware now counts as a modification. That means it gets recommissioned to the extent needed and signed off on a modification certificate, the same as adding devices. The thinking is simple: a small change to the panel can upset cause and effect, zoning or outputs elsewhere.
So if you're asked to "just update the panel software" on a service visit, it isn't just a service visit any more. Price and paperwork it accordingly. The which certificate finder walks through which certificate goes with which job.
Extensions have to meet the current standard
This was already the direction of travel, but clause 45.1 is clear: an extension has to conform to the current standard in its own right, even if the rest of the system is older. Responsibility sits with someone competent in fire alarm design, not just installation (clause 45.2). The extended work is recommissioned as far as needed to check its effect on the existing system, including battery capacity, radio signal strength and cause and effect, and gets a signed extension certificate (clauses 45.3 and 45.4).
Battery capacity is the one that catches people out: add a dozen sounders and VADs and the original batteries may no longer cover 24 hours plus 30 minutes. Run the numbers again with the battery calculator.
Variations: all recorded, and two never allowed
In the 2025 edition every variation has to be recorded, in the log book as well as on the certificate. And two variations are no longer acceptable at all:
- leaving out a zone plan on a storey with more than one zone;
- no alarm receiving centre link in residential care or supported housing that needs one.
If a client asks you to "variation out" either of those, the answer is no. The fire alarm log book has a page for variations.
Cyber security
The 2025 edition expects the system's communications to be protected: communications cabinets locked, anti-tamper patch plugs, and authentication before any remote connection. Before anyone is given remote access to read, control or change the system, a risk assessment is needed. If you offer remote servicing, have that assessment ready.
Batteries: date them
Clause 24.3.3 recommends marking each standby battery with the date it was fitted. A permanent marker on the case is fine. The sizing method (Annex E) and standby times (clause 24.3.5) are as before; our battery size guide goes through them with a worked example.
Certificates
Annex G still holds the model certificates: design, installation, commissioning, acceptance, verification, inspection and servicing, and extension or modification. If your certificates were laid out for the 2017 edition, check they now cover firmware updates as modifications and have room for every variation.
Where to look things up
The quick reference guides cover BS 5839-1:2025 question by question, in plain words, with a switch for the technical version, and they work on your phone with no signal.
For guidance only. This is a summary, not the standard: always check against your own copy of BS 5839-1:2025.
Kerova's fire alarm certificates are built around BS 5839-1:2025, with a place to record every variation.
Common questions
When did BS 5839-1:2025 replace the 2017 edition?
In April 2025. Most of the standard reads the same; the changes that matter on site are the sleeping-room detection in L2 and L3, detection in stairway lobbies, firmware updates counting as modifications, extensions meeting the current standard, how variations are recorded, and cyber security.
Do existing systems have to be upgraded to the 2025 edition?
No. The changes are not retrospective: a system that met the 2017 edition when it went in does not have to be upgraded because the standard changed. New work, extensions and modifications have to meet the 2025 edition.
Is a panel firmware update a modification under BS 5839-1:2025?
Yes. Updating the control panel firmware now counts as a modification, so it is recommissioned as far as needed and signed off on a modification certificate.
Which variations are no longer allowed?
Leaving out a zone plan on a storey with more than one zone, and having no alarm receiving centre link in residential care or supported housing that needs one. Every other variation has to be recorded in the log book as well as on the certificate.
This guide is general information for UK fire & security companies, not legal or engineering advice. Always work to the current edition of the relevant standard and your own competent-person judgement.
Doing it on site?Doing the fire alarm certificate? Do it on your phone with Kerova's fire alarm certificate software, part of its fire and security software. The register, readings and result are built into the certificate itself.