Calculator · Intruder alarm · PD 6662
Intruder alarm battery calculator
Quick answer
The battery has to run the system through a mains failure for the standby time the grade needs, then sound the alarm. This calculator uses the same formula as the fire alarm one: 1.25 (ageing) × (standby current × standby hours + 1.75 (de-rating) × alarm current × alarm time). It's an estimate; check the panel maker's figures.
Choose the security grade, then enter the standby current and the alarm current. You get an estimate of the battery capacity needed to run through a mains failure and then sound the alarm, with the working and the next common battery size. It is an estimate, not a compliance check.
Result
Enter the standby and alarm currents to see the result.
Working
Ah = ageing × (I1 × T1 + D × I2 × t)
- I1 is the standby current: everything the battery feeds while the mains is off. Add the panel, keypads, detectors, the external sounder's quiet current and the communicator.
- I2 is the alarm current: the same total, plus what the sounder and communicator draw when the alarm sounds.
- T1 is the standby period. t is the alarm period, added on top of the standby period, and is 30 minutes unless you change it.
- D is the de-rating factor, 1.75 unless you change it under Advanced. It is applied to the alarm current only, because a battery gives less capacity when it is drained quickly.
- Ageing allows for the battery losing capacity over its life. This page starts at 1.25. Some panel makers use less, for example 85% usable capacity, which is about 1.18.
- Standby hours (EN 50131-6 / PD 6662): Grades 1 and 2 need 12 hours. Grades 3 and 4 need 60 hours, or 30 hours where mains failure is signalled to an alarm receiving centre (ARC).
- Recharge: panel makers' manuals give a maximum of 72 hours for Grades 1 and 2 and 24 hours for Grade 3.
The method is the same formula as the fire alarm battery calculator (BS 5839-1, Annex E), used here for intruder alarms too. Check it against your panel maker's figures and your copy of the standard.
For a fire alarm panel, use the fire alarm battery calculator. It uses the same method, with the fire alarm standby hours. For the grade descriptions, see intruder alarm security grades explained.
Worked example
Grade 2 system, standby current 200 mA, alarm current 900 mA, 30 minutes of alarm:
- Standby: 0.2 A × 12 h = 2.4 Ah
- Alarm: 1.75 × 0.9 A × 0.5 h = 0.7875 Ah
- With ageing: 1.25 × (2.4 + 0.7875) = 3.98 Ah, so fit the next common size, 7 Ah.
Grade 3 system, mains failure signalled to an ARC (30 hours), 350 mA standby and 1.2 A in alarm: 14.44 Ah, so a 17 Ah battery.
Use it on site: the intruder alarm certificate app in Kerova records the battery readings and the standby time for the grade on the certificate.
Common questions
How many hours does an intruder alarm battery need to last?
With the EN 50131-6 / PD 6662 figures: 12 hours for Grades 1 and 2. For Grades 3 and 4, 60 hours, or 30 hours where mains failure is signalled to an alarm receiving centre.
Why is there an ageing factor?
A battery loses capacity as it ages, so the sum is multiplied up to leave room for that. This page starts at 1.25; some panel makers use a little less. You can change it under Advanced.
What battery size should I fit?
The next common size at or above the answer. The result shows it, but check the panel's battery space and its maximum charger capacity in the maker's manual.
Can I do this on site in the Kerova app?
Yes. The intruder alarm certificate records the battery readings against the standby time for the grade, on your phone, and the result goes on the certificate.
For guidance only. Always check against the current edition of the standard and the manufacturer's data.