Fire alarm · BS 5839-1
How to work out a fire alarm battery size
Quick answer
BS 5839-1 Annex E gives the minimum standby battery capacity as Cmin = 1.25 × (T1 × I1 + D × I2 × T2): the standby hours times the standby current, plus the de-rating factor (1.75 unless the battery maker says otherwise) times the alarm current and alarm time, all times 1.25 for ageing. The answer is in amp hours.
The formula
BS 5839-1 Annex E gives the minimum standby battery capacity as:
Cmin = 1.25 × (T1 × I1 + D × I2 × T2)
| Symbol | What it is |
|---|---|
| Cmin | The minimum battery capacity when new, in amp hours (Ah), at the 20-hour rate and 20 °C |
| 1.25 | The ageing factor, allowing for the battery losing capacity over its life |
| T1, I1 | The standby period in hours, and the standby current in amps (the whole system on battery, no alarm) |
| T2, I2 | The alarm period in hours, and the alarm current in amps (the whole system in alarm) |
| D | The de-rating factor, 1.75 unless the battery maker gives another figure |
In words: work out the charge the system uses on standby, add the charge it uses in alarm (allowing for the battery giving less when it is drained quickly), then add a quarter for the battery losing capacity as it ages.
The usual starting figures are 24 hours of standby and 30 minutes of alarm. The result is the same as under the 2017 method.
How long the battery has to last
BS 5839-1:2025 sets the standby time in clause 24.3.5:
- Most category L and M systems: 24 hours of standby, then 30 minutes of alarm in every alarm zone.
- With an automatically started standby generator feeding the system: 6 hours of standby is enough.
- Category P (property protection): 24 hours more than the longest time the building is likely to be empty, up to 72 hours in total, then 30 minutes of alarm. That can come down to 24 hours if the building is staffed, or a mains fault is reported automatically to an alarm receiving centre.
If you are not sure, design for 24 hours plus 30 minutes. It is what the standard expects for most buildings, and it is what the calculator starts with.
A worked example
A panel draws 250 mA on standby (panel plus loop devices) and 750 mA in alarm with the sounders running. Standby is 24 hours and the alarm period is 30 minutes (0.5 hours).
- Standby charge: 24 h × 0.25 A = 6 Ah
- Alarm charge: 1.75 × 0.75 A × 0.5 h = 0.656 Ah
- Total: 6 + 0.656 = 6.656 Ah
- With ageing: 1.25 × 6.656 = 8.32 Ah
That is the minimum. A battery has to be at least that big, so in practice you pick the next size up, never the one just under. With common sizes of 7, 12, 17, 24, 38 and 65 Ah, 8.32 Ah means a 12 Ah battery: a pair of 7 Ah batteries would not do.
The free battery calculator does these steps and shows the working, picks the next common size and copies the result, so you can print it with the certificate.
Where the currents come from
The sum is only as good as the currents you put in. Use the figures from the panel's data, not a guess. The standby current is everything the battery feeds while the mains is off. The alarm current is the same, plus what the sounders and any communicator draw when the alarm sounds.
- Take the panel's own quiescent current from its manual, then add the loop devices' standby currents from their datasheets. Do not guess a round number.
- In alarm, add every sounder and visual alarm device (VAD) at the volume and flash rate it is actually set to. VADs are often the biggest load.
- Include anything the panel powers: interfaces, repeaters, remote signalling.
- On a big system, check the volt drop to the furthest sounder on battery as well as the capacity. The DC voltage drop calculator does the cable side.
Check your panel's maximum battery size and charger rating as well, because a bigger battery is no use if the charger cannot recharge it.
Fitting, dating and checking the batteries
- Use a proper sealed lead-acid standby battery rated for at least four years in service, never a car battery, with a charger that can bring it back to full within 24 hours (clauses 24.3.1 to 24.3.4).
- Mark the date on the battery. BS 5839-1:2025 (clause 24.3.3) recommends marking batteries with their installation date. Writing it on the casing in permanent marker is acceptable.
- On every service, check the charger voltage and the batteries' condition, and log the readings. The fire alarm service checklist has the checks in order.
- Replace them on age as well as on test. Most makers quote around four years at 20 °C, less in a warm riser cupboard.
On a Kerova certificate the engineer picks the month and year from each battery label. Kerova shows the battery's age, says “Replace soon” six months before the replacement age (four years unless your firm changes it in Settings), and when the certificate is signed an over-age battery becomes a repair to quote for (unless your firm has switched that off).
Wireless systems
Radio devices are different: each one needs two independent power sources (mains plus a battery, or two batteries), and the panel should show a fault when a device's power is down to its last 30 days plus 30 minutes in alarm (clause 26.2). Check those battery warnings on every visit.
What about intruder alarms?
Our intruder alarm battery calculator uses the same formula with the intruder standby hours from the grade. That is an estimate, not a rule in PD 6662 or BS EN 50131. Check the panel maker's own figures for the job.
Common questions
What is the formula for fire alarm battery capacity?
Cmin = 1.25 × (T1 × I1 + D × I2 × T2), from BS 5839-1 Annex E. T1 and T2 are the standby and alarm periods in hours, I1 and I2 the standby and alarm currents in amps, 1.25 the ageing factor and D the de-rating factor, 1.75 unless the maker gives another figure.
How many hours of standby does a fire alarm battery need?
For most systems, 24 hours of standby and then 30 minutes of alarm. With an automatically started standby generator, 6 hours of standby is enough. Category P systems can need up to 72 hours, depending on how long the building may be empty.
What size battery do I need for 250 mA standby and 750 mA alarm?
8.32 Ah as a minimum, using 24 hours of standby and 30 minutes of alarm. The next common battery size up is 12 Ah.
What is the de-rating factor?
A battery gives less than its rated capacity when it is drained quickly. The formula applies a de-rating factor D to the alarm current to allow for that. It is 1.75 unless the battery maker gives another figure.
Can I use a car battery as a fire alarm standby battery?
No. BS 5839-1 asks for a rechargeable standby battery rated for at least four years in service, with a charger that can recharge it to full within 24 hours. An engine-starting battery is not suitable.
This guide is general information for UK fire & security companies, not legal or engineering advice. Always work to the current edition of the relevant standard and your own competent-person judgement.
Doing it on site?Doing the fire alarm certificate? Do it on your phone with Kerova's fire alarm certificate software, part of its fire and security software. The register, readings and result are built into the certificate itself.
Start free trial