Calculator · Fire alarm · BS EN 60228 cable data
Fire alarm loop resistance calculator
Quick answer
Loop resistance is the resistance per metre of the cable times the length of the whole loop, out from the panel and back, for both cores. Compare it with the maximum in the panel maker's manual.
Enter the cable size and the length of the whole loop, out from the panel and back. You get the loop resistance of both cores, with every step shown. Add the panel maker's maximum from its manual and it says whether the loop is within it, and the longest loop you can run.
Result
Enter the loop length to see the loop resistance.
Working
R_loop = r × L × 2 × k
- r is the resistance of one core per metre. It comes from the cable size (BS EN 60228, plain copper, at 20 °C): 18.1 Ω per km for 1.0 mm², 12.1 for 1.5 mm² and 7.41 for 2.5 mm².
- L is the whole loop length: out from the panel, round every device and back to the panel.
- The loop has two cores and each runs the whole length, so the sum uses × 2.
- k is 1 at 20 °C. A warmer cable has more resistance: 0.4% more for each degree, so 1.20 at 70 °C.
The figures are the most a cable may have, so a real loop usually measures a little lower. The maximum loop resistance is set by the panel maker, not by a standard.
This works out the resistance from the cable only. On site, measure the loop with a meter as well and record the reading. For a conventional sounder circuit, use the sounder circuit calculator.
For guidance only. Always check against the current edition of the standard and the manufacturer's data.