Quick reference · Fire detection and alarm systems in domestic premises
BS 5839-6: quick reference
How fire detection and fire alarm systems are designed, installed, commissioned and maintained in homes: single-family houses, houses in multiple occupation (HMOs), sheltered and supported housing and self-catering accommodation.
The rules for smoke and heat alarms in people's homes, rented flats and shared houses.
BS 5839-6:2019+A1:2020. The 2019 edition removed grades B and E and split grades D and F. Amendment 1 (November 2020) updated the model certificates and added a warning that some children may not wake to an alarm.
Confirmed two or more sources agree, or a source quotes the standard. Check one source, or a detail that could not be confirmed. Check it against the standard.
Design, installation, commissioning and maintenance in domestic premises, including single-family homes, HMOs, sheltered housing, supported housing and self-catering. Boarding houses are outside it.
It is the standard for alarms in homes, shared houses and sheltered housing. Boarding houses use the non-domestic standard.
Grade A is detectors, sounders and control equipment to BS EN 54 with standby power. Grade C is detectors and sounders on a common power supply with central control. Grade D1 is mains-powered alarms with a tamper-proof standby battery. Grade D2 is mains-powered with a user-replaceable standby battery. Grade F1 is battery-only with tamper-proof batteries. Grade F2 is battery-only with user-replaceable batteries.
A is a full fire alarm system. C is a smaller system on one power supply. D is mains-powered alarms with a backup battery. F is battery-only alarms. The 1 means the battery cannot be taken out, the 2 means it can.
A and C are systems, D is mains alarms with a backup, F is battery-only alarms. The 1 means the battery is sealed in.
LD1 is detection in all circulation areas on escape routes and in all rooms except those with negligible risk. LD2 is circulation areas on escape routes plus rooms with high risk, such as the kitchen and the principal habitable room. LD3 is circulation areas on escape routes only.
LD1 is detectors nearly everywhere. LD2 is the hallways and stairs plus the higher-risk rooms like the kitchen and living room. LD3 is the hallways and stairs only.
LD1 covers the escape routes and nearly every room, LD2 the escape routes and the high-risk rooms, and LD3 the escape routes only. No alarms in bathrooms.
Table 1 gives Grade D1 with LD2 for a new, materially altered, or existing rented single-family home up to three storeys, and Grade D2 with LD2 for a new owner-occupied home up to three storeys. Existing owner-occupied homes can be lower, for example F2 with LD3. A single house does not simply move to Grade A once it reaches four storeys — it is converted buildings with separate self-contained flats, or other buildings with communal areas, that bring Grade A into play for the shared parts, alongside a lower grade inside each flat.
A rented house normally gets mains alarms with a tamper-proof battery (D1). An owner-occupied new build gets mains alarms with a replaceable battery (D2). Older owner-occupied homes can use a simpler grade. A full system (Grade A) comes in for the shared parts of a building split into separate flats, not just because a single house is tall.
Corroborated against two manufacturer/trade technical summaries, not the standard itself. Check Table 1 for a specific property, especially a converted or multi-occupancy building.
A shared house (an HMO where tenants share living space rather than having separate flats) typically gets D1 with LD2, much like an ordinary rented house. Where a building has been converted into separate self-contained flats, the shared parts (hallways, stairs) get Grade A, with a lower grade inside each individual flat. In sheltered housing, each dwelling is typically D2 with LD2 (existing) or LD1 (new/materially altered), while the communal areas get Grade A; sheltered housing's category was raised from LD2 to LD1 in the 2019 edition. Detectors can normally be left out of roof voids unless there is a specific fire hazard there.
A shared house gets alarms much like an ordinary rented home. A house converted into separate flats needs a full system in the shared hallways and stairs, with a simpler system inside each flat. Sheltered housing works the same way — a simpler system in each person's home, a full system in the shared areas — and now needs alarms in nearly every room of the home, not just the escape routes.
Corroborated against two manufacturer/trade technical summaries, not the standard itself. Check Table 1 for a specific building.
The kitchen gets a heat alarm specifically, not a smoke or CO alarm — cooking fumes make smoke and CO detectors prone to nuisance alarms there. The principal habitable room (usually the main living room) gets a smoke alarm or a carbon monoxide alarm. Bathrooms, toilets and shower rooms should not have alarms in any category, because steam causes nuisance alarms. Detectors may normally be left out of roof voids unless there is a specific fire hazard there.
Put a heat alarm in the kitchen — not a smoke or CO alarm, since cooking sets those off. Put a smoke or CO alarm in the main living room. Never put alarms in bathrooms, toilets or shower rooms, because steam sets them off.
Mounted on the ceiling, at least 300 mm from walls, light fittings or any other obstruction, and within 3 m of every bedroom door. On a sloping ceiling, smoke alarms go no more than 600 mm down from the apex and heat alarms no more than 150 mm down; on a staircase, the alarm goes on a flat section of ceiling at the top and bottom, not on a sloped ceiling directly above the stairs. A ceiling beam shallower than 10% of the room height is treated like any other obstruction — the alarm sits at least twice the beam's depth away, or 500 mm, whichever is less; a beam deeper than that is treated as a wall, with an alarm needed on each side of it.
Fit alarms on the ceiling, well clear of walls and lights (300 mm), and close to bedroom doors (within 3 m). On a sloping ceiling, near the top — 600 mm down for smoke, 150 mm for heat. On a staircase, put the alarm on the flat ceiling at the top or bottom, not on a sloped section above the stairs. A shallow ceiling beam just needs extra clearance; a deep one needs an alarm on each side, like a wall.
Fit alarms on the ceiling, clear of walls and lights, and within 3 m of every bedroom door.
Ceiling-mounted, 1 to 3 m from the fuel-burning appliance, and at least 300 mm from walls, light fittings or other obstructions, same as a smoke or heat alarm. If the appliance is in a cupboard or other confined space, put the alarm on the ceiling just outside. Where there's a CO risk but no specific appliance to measure from (such as fumes entering from an integral garage), mount it at breathing height, or near the bed head in a bedroom.
Put a CO alarm 1 to 3 m from the boiler or fire, ceiling-mounted, clear of walls and lights. If the appliance is in a cupboard, put the alarm on the ceiling just outside the door. Without a specific appliance to aim for, mount it at breathing height, or near the bed in a bedroom.
Fit a carbon monoxide alarm on the ceiling 1 to 3 m from the appliance, or just outside if it is in a cupboard.
Alarms in a property should be interlinked — wired, radio-linked, or a hybrid of both — depending on the grade, so that one alarm triggering sets all of them off. Mains-powered CO alarms to BS EN 50291 may be interlinked with the fire system too, if the manufacturer allows it.
Alarms should talk to each other, so that when one goes off they all do. This can be by cable, by radio, or a mix of both. A mains-powered CO alarm can often join the same interlinked system, if the maker says it's compatible.
D1 and F1 have a tamper-proof standby battery, meaning it isn't meant to be removed by the occupant. D2 and F2 have a user-replaceable battery. If there's doubt about whether an occupant would actually replace a D2 or F2 battery when needed, the standard steers towards a tamper-proof version instead.
In D1 and F1 the battery is sealed in, so an occupant can't take it out. In D2 and F2 it can be replaced. If there's any doubt a battery would actually get changed, use the sealed version.
No. The 75 dB(A) at the bed head is from BS 5839-1 for non-domestic sleeping areas. BS 5839-6 sets its own domestic sound levels, which could not be confirmed here.
The bed head figure comes from the non-domestic standard, not this one. Check BS 5839-6 for the home figure.
Grade A: tested weekly, like a non-domestic system, and serviced at intervals no longer than 6 months, following BS 5839-1 Clause 45. Grades C, D and F: tested monthly, usually by pressing the test button, with service intervals otherwise set by the manufacturer. Every test and service result goes in a log book, and a signed certificate is issued on completion of a service.
Full systems (Grade A) are tested weekly and serviced at least every 6 months, same as a non-domestic fire alarm. Smaller alarm sets are tested monthly, usually by pressing the test button. Every test and service gets written in a log book, with a signed certificate when it's serviced.
Grades B and E were removed, grade C was redefined, D and F were split into D1 and D2 and F1 and F2, Table 1 was revised, the text was aligned with BS 5839-1:2017, and a new table on testing and servicing by grade was added. Sheltered housing went from LD2 to LD1.
The 2019 edition tidied up the grades, split D and F into two each, and raised sheltered housing to LD1.
Two things: a new warning, for householders and on manufacturers' product documentation, that some children may not wake to the alarm tone while asleep, with advice on planning for that; and updated model certificates — an acceptance certificate for Grade A, and a design, installation and commissioning certificate for Grades C, D and F.
It added a warning that some children sleep through alarms, which now has to appear on the product documentation too, plus new certificate forms.
Under the Smoke and Carbon Monoxide Alarm (England) Regulations 2015, as amended in 2022 (from 1 October 2022): at least one smoke alarm on every storey used as living accommodation, and a carbon monoxide alarm in any room with a fixed combustion appliance, except gas cookers. Alarms must be checked as working at the start of a tenancy, and the landlord repairs or replaces a faulty alarm once told. Local authorities can issue a civil penalty of up to £5,000 after a 28-day compliance window. It applies in England only, and social landlords are now covered.
Landlords in England must fit a smoke alarm on each floor people live on, and a CO alarm wherever there is a fuel-burning appliance. They must check alarms work at the start of each tenancy and fix faulty ones.
No. The regulations set a legal minimum, which is lower than the grade and category BS 5839-6 gives for many properties. The standard is a code of practice, not law.
The law is the least you must do. The standard describes good practice and often asks for more.