Quick reference · The IET Wiring Regulations, as they affect alarm and CCTV engineers
BS 7671 (for alarm and CCTV work): quick reference
The UK rules for electrical installations. This guide only covers the parts that alarm, CCTV and access control engineers meet, such as cable resistance and voltage drop.
The UK wiring rules. This page only picks out the parts that matter when you install alarms, cameras and door entry.
BS 7671:2018+A4:2026. Amendment 4 was published on 15 April 2026. Amendment 3 (2024) stays valid until 15 October 2026.
Confirmed two or more sources agree, or a source quotes the standard. Check one source, or a detail that could not be confirmed. Check it against the standard.
BS 7671 uses a temperature coefficient of 0.004 per °C for copper, so a conductor at 70 °C has about 1.20 times its 20 °C resistance. The true figure for copper is about 0.00393 per °C.
Copper cable resists current a bit more when it is warm. At 70 °C, allow about 20% more resistance than at 20 °C.
A hot cable resists more. At 70 °C allow 20% more than at 20 °C.
The current goes out and back, so the loop resistance is twice the run length times the resistance per metre. The drop is the current times the loop resistance.
Count the cable both ways. Voltage lost = current × (resistance per metre × 2 × length).
Count the cable both ways. The voltage at the load is the supply less what is lost in the cable.
Band I is extra-low voltage, up to 50 V a.c. or 120 V ripple-free d.c. Alarm, control and telecom circuits are usually Band I. Band II runs up to 1,000 V a.c.
Band I is low-voltage circuits such as alarms and phones, up to 50 V a.c. or 120 V d.c. Band II is mains-level circuits.
Band I and Band II circuits must not share a wiring system (regulation 528.1), unless all the conductors are insulated for the highest voltage present, or they run in separate compartments or conduits.
Do not run alarm cables and mains cables together in the same trunking or conduit, unless every cable is insulated for the higher voltage or they are in separate compartments.
Band I and Band II circuits must not share a wiring system, unless all the cables are insulated for the higher voltage or are in separate compartments.
At least 100 mm from power (Band II) cables, for Band I cables such as telecom and data cabling in ducts or underground (regulation 528.2). Where 100 mm cannot be kept, either a fire-retardant partition is fitted between the cables (bricks, shaped blocks, protective cable conduit), or, where the cables cross, mechanical protection is placed between them (conduit, concrete cable-protecting caps, shaped blocks).
Keep telecom and power cables 100 mm apart in ducts and underground. If you cannot keep that gap, fit a fire-retardant partition between them, or, where they cross, mechanical protection like conduit or a concrete cap.
Test at 500 V d.c. and expect at least 1 megohm for circuits up to 500 V. For SELV and PELV circuits, test at 250 V d.c. and expect at least 0.5 megohm (Table 64).
Test ordinary circuits at 500 V and expect at least 1 megohm. Test extra-low voltage circuits at 250 V and expect at least 0.5 megohm.
Yes. Disconnect surge protectors and sensitive electronics before insulation testing. If that is not possible, 250 V d.c. may be used, but the 1 megohm minimum still applies.
Take out or disconnect sensitive equipment before testing. If you cannot, use 250 V, but the result must still be at least 1 megohm.
A dedicated circuit, uninterrupted and solely for the fire alarm, taken from a point close to the building's main isolating device, with as few protective and isolating devices as possible between that origin and the panel's local isolator. No RCD is fitted unless BS 7671 itself requires one for safety, and even then it must not be able to isolate the fire alarm's own supply. The local isolator is labelled 'FIRE ALARM — DO NOT SWITCH OFF', and every other switch or protective device back to the origin carries 'WARNING — THIS SWITCH ALSO CONTROLS THE SUPPLY TO THE FIRE ALARM SYSTEM', so nobody isolates it by accident at a sub-board. The cable itself should be fire-resistant to the same grade as the fire alarm's own cabling, in the same colour, per BS 5839-1. Where BS 7671 and the fire alarm standard conflict, the fire alarm standard takes precedence.
Give the panel its own dedicated supply, as close as possible to the building's main switch, with as few other switches in the way as possible. Don't fit an RCD unless the wiring regs actually require one, and even then it mustn't be able to cut the fire alarm's power. Label the panel's own isolator 'DO NOT SWITCH OFF', and put a warning on every other switch between there and the origin, so nobody switches the fire alarm off by mistake. Use proper fire-resistant cable for the supply, matching the fire alarm's own cable.