Quick reference · Electronic access control systems

BS EN 60839-11-1: quick reference

The minimum functions, performance and test methods for electronic access control systems and components used for entry and exit in and around buildings.

What a door entry or access control system and its parts must be able to do, and how they are tested.

BS EN 60839-11-1:2013. BSI and the IEC list the 2013 edition as current, and no newer edition was found. Design, installation and maintenance guidance is in the companion BS EN 60839-11-2.

Confirmed two or more sources agree, or a source quotes the standard. Check one source, or a detail that could not be confirmed. Check it against the standard.

What does the standard cover?

The minimum functions, performance requirements and test methods for electronic access control systems and components used for entry and exit in and around buildings. It includes logging, identification and control of information.

What an access control system and its parts must do, and how they are tested. It covers who can go where, and the records kept.

Confirmed

What does it leave out?

The door actuators and sensors, such as electric openers, locks, turnstiles and barriers, which have their own standards, and the sending of intruder or hold-up signals off the premises. The risk analysis is not part of the standard, and the risk levels shown are for information only.

It does not cover the locks, barriers and turnstiles themselves, or sending alarms off the site. It does not tell you how to do the risk assessment.

Confirmed

What subjects does it cover?

A grade classification table, the interface at each access point including door release timing, display, alert and logging, recognition (credential) requirements, duress signalling, overriding, system self-protection, power supply, environmental and EMC immunity, and test methods.

It covers the grades, how the door opens, alerts and logs, how people are recognised, duress alarms, overrides, tamper protection, power, weather and interference, and testing.

Confirmed

What are the four grades?

There are four security grades, applied to each access point rather than to the whole building: Grade 1 is low risk, Grade 2 is low to medium, Grade 3 is medium to high and Grade 4 is high risk.

The grade says how much risk a door is protecting against, from 1 (low) to 4 (high). Each door has its own grade, not the whole building.

The grade shows the level of risk an access point is protecting against. Each door has its own grade.

Confirmed

What does each grade look like in practice?

Grade 3, for example, is generally described as a high level of security and resilience, suitable for medium- to high-risk sites such as public venues, military facilities and critical infrastructure. Installers commonly illustrate the lower grades with a basic stand-alone code, card or fob lock, and the higher grades with networked systems using two-factor authentication or biometrics — these specific examples are illustrative, not direct quotes from the standard's own text.

A simple stand-alone code lock is typically a lower grade. A networked system with two ways of proving who you are, or biometrics, suits the higher grades, for places like public venues or critical infrastructure.

The named technology examples are trade illustrations, not the standard's own wording — check the standard for what each grade formally requires.

Check

What does it say about power supplies?

It has a power supply table and tests for standby duration, the charger and standby capacity, and low or missing battery detection. In practice, access control power supply units are very commonly specified against BS EN 50131-6 (the intrusion-alarm power supply standard) rather than a figure unique to -11-1 — which, if followed, gives the same standby hours as the matching intruder alarm grade: 12 hours for Grade 1 or 2, 30 for Grade 3, 60 for Grade 4.

There are rules for backup power and tests for it, including spotting a low or missing battery. In practice, access control power supplies are usually built to the same power supply standard as intruder alarms, giving the same standby hours: 12 hours for Grade 1 or 2, 30 for Grade 3, 60 for Grade 4.

The standby hours are those of the commonly-referenced BS EN 50131-6, not independently confirmed as -11-1's own figures.

CheckAccess control door power supply calculator →

What environmental tests apply?

Components have environmental and electromagnetic immunity requirements for indoor or outdoor use. It refers to IEC 60529 (IP ratings), IEC 62262 (IK impact ratings) and IEC 62599-1 and -2.

Parts must cope with the weather, knocks and electrical interference where they are fitted.

Confirmed

What if part of the system is also an intruder or CCTV system?

If part of an access control system also forms part of an intruder, hold-up or video surveillance system, that part must also meet the standards for those systems.

If a part does another job too, such as a door contact that is also an alarm sensor, it must meet the standard for that job as well.

Confirmed

Where is the design and maintenance guidance?

In the companion standard IEC 60839-11-2 (BS EN 60839-11-2:2015 in the UK), not in -11-1.

How to design, install and look after the system is in a separate standard, part 11-2.

Confirmed

Which standards apply to doors on escape routes?

BS 7273-4 covers how the fire alarm releases electrically locked doors. BS EN 179 is for escape hardware used by trained people and BS EN 1125 is for panic exit hardware in public areas. BS EN 13637 covers electrically controlled exit systems on escape routes, and BS 7273-4 now refers to it for any electrically locked escape door.

Doors on escape routes follow other standards as well: one for the fire alarm release, and others for the panic bars and exit hardware.

ConfirmedFail-safe and fail-secure locks →

Can magnetic locks be used?

They are not banned outright. They are acceptable on non-escape doors, or where escape stays a single action. Where an electrically locked door is on an escape route, BS 7273-4 now points to BS EN 13637, which requires the door to release in a single actuation within 100 milliseconds, with the lock itself able to release under at least 100 kg of sideload. A lock that adds a second action to escape is a problem. The installer is responsible for challenging a client's specification at design stage when it conflicts with the standards.

Magnetic locks are fine on doors that are not escape routes, or where getting out is still one simple action. On an escape door, the release has to happen in a tenth of a second from a single action, and the lock has to let go even if someone's leaning on the door. If a client asks for something unsafe, the installer should speak up.

ConfirmedAccess control lock cable calculator →

Other guides: BS 5839-1, BS 5839-6, BS 5266-1 and BS EN 1838, BS 5306 (extinguishers), BS EN 50131-1 and PD 6662, BS 8418, BS EN 62676-4, BS 7273-4, BS 7671 (for alarm and CCTV work). Not sure what a word means? Explain this text or see the glossary.

For guidance only. Always check against the current edition of the standard and the manufacturer's data.